1. Performance Characteristics and Application Scope

MPUPC500-220S48 is a rechargeable power supply specifically designed and produced by our company for distribution network automation. This power supply boasts several advantages, including compact size, high conversion efficiency, stable performance, primary-secondary isolation, and high isolation strength. The product features a metal-encased modular design, offering dust and moisture resistance as well as strong anti-interference capabilities. Its input and output terminals are designed as wiring terminals for easy connection. With strong grid adaptability, this product can operate within a wide range of input voltages. It also incorporates protection functions such as output short circuit and overvoltage protection. Additionally, this product boasts an intelligent charging feature, enabling it to charge external 48V batteries.

During AC power outages, the batteries can provide uninterrupted power to the load, with a protection function against battery overdischarge. It also features a power status display and a battery activation function, allowing for manual or automatic activation and maintenance of the battery through external signals. This power supply is ideal for use in power distribution network automation systems, intelligent power distribution boxes, ring main units, and other industries requiring uninterrupted DC power supply and high performance

2. Technical Parameters

 

 Input Characteristics

Item

Test Condition

Min

Typical

Max

Voltage Input range

Full Output Load

165.0

220.0

265.0

Input Voltage Range

Full Output Load

200.0

300.0

375.0

Frequency (Hz)

AC Input

40

50

60

 

Output Characteristics

Item

Test Condition

 

Min

 

Typical

 

Max

 

Output Voltage

Full-range input, normal typical output load

53.2

53.5

53.8

AC power failure, battery supply

42.0

--

53.8

 

Output Current

Full-range input, excluding charging current

0

5.6

--

Full-range input, transient inrush current ≤10S

0

--

13.0

Ripple & Noise

Full-range input, normal typical output load

--

--

400

 Source Effect

Full-range input, normal typical output load

--

--

±1.0

Ripple & Noise

Typical input, load varies between 10%~100% of normal typical load

--

--

±1.0

 

Battery Float Charging Voltage

Io=4.0A,IB=0.01A

Full-range input, Io=4.0A,IB=0.01A

53.2

53.5

53.8

Battery Constant Current

Charging Current

Full-range input, typical load

1.00

1.20

1.40

Battery Activation

Completion Voltage

Full-range input, normal typical output load

44.0

45.0

46.0

Battery Undervoltage

Alarm Voltage

Full-range input, normal typical output load

44.0

45.0

46.0

Battery Discharge Circuit

Internal Resistance

Full-range input, normal typical output load

42.0

43.0

44.0

Battery Discharge Circuit

Internal Resistance

 

Discharge current 15A

--

0.05

--

Maximum Battery

Discharge Current

Discharge time ≤30S

--

--

15

Activation Contact TimeDischarge Current

Remote activation start/exit

--

0.5

1.0

Remote battery exit

--

0.5

1.0

Output Overvoltage Alarm

 

59.0

60.0

61.0

Output Short-circuit Protection

Full-range AC input

 Turn off power output and

cancel automatic restart

 

General Characteristics

Item

Test Condition

Min

 

Typical

 

Max

Temperature Coefficient

 Full-range input, normal typical output load

--

--

±0.02

 

 Insulation Resistance (MΩ)

 

500VDC Test voltage 500VDC

Input to Output

50

--

--

Input to Case

50

--

--

Output to Case

50

--

--

 

 Efficiency

Typical AC input, normal typical output load, fully charged battery

 

--

 

84

 

--

 

 

 Isolation Voltage

Leakage current 5mA, power frequency 50Hz, no breakdown or flashover for 1min

 Input to Output

1500Vac

Input to Case

1500Vac

Output to Case

500Vdc

 

Overall Dimension

168.0×110.0×45.0

Ambient Temperature

 

-25

--

+65

Operating Case Temperature

 

-25

--

+85

Storage Temperature

 

-40

--

+105

Weight

 

--

1.5

--

 

Mean Time Between Failures

Room temperature

80000

--

--

When the ambient temperature exceeds 55℃, derated operation is required, or forced cooling methods such as air cooling and case-attached heat dissipation should be adopted to ensure that the module case temperature does not exceed 85℃.

 

1. Internal Circuit Principle of Power Supply

 

Power supply internal isolation diagram
 

1、 Charging  &  Working  Indicator 

2、 Battery Discharge   Indicator 

3、 Battery   Activation   Indicator 

4、 Battery   Undervoltage   Indicator 

5、 Power Fault (Overvoltage) Indicator

6、 Manual Activation Start Key

7、 Manual Activation Exit Key

8、 Manual Battery Input Key

9、 Manual Battery Exit Key

10、Terminal

 

5. Wiring Instructions

 

Wiring instructions: K1 K2 K3 are relay contacts controlled by the user's CPU and other components (contact capacity is not required, but cannot be replaced by optocouplers). The load is the user's normal load, and the battery is a 48V battery pack. The capacity of the wiring terminal is 300V/15A. Please refer to the following instructions for specific usage.

 

 